|cooling tower water treatment|cooling tower water treatment|process water filtration|industrial water filtration systems Our "A" Series is used for In-line applications to ensure a continuous or intermittent flow – the flow can be maintained during backwash operation. When one vessel is in backwash mode the remaining vessels ensure the selected flow. The VORTISAND® cooling water filter is available in a variety of materials and components depending on each application requirements. Sonitec manufactures customized systems based on your specifications.

We recommend the following maintenance schedule for your VORTISAND® cooling tower filter:
Once a day, a technician should take the reading on the backwash counter and cooling tower filter inlet/outlet pressure, and enter the information into a logbook. We have included a suggested log sheet at the end of this section.
Once a week, a manual backwash should be initiated. During the backwash cycle, the opening and closing of the valves should be verified.
In the Spring and in the Fall seasons, verify the media level by opening the Victaulic coupling at the back of the cooling tower filter. Please refer to your Operation and Maintenance manual for complete procedure.

Recent studies carried out using laser particle counters have shown that 85-95% of the particles present in the recirculation water of either closed loops (evaporator circuit) or open loops (cooling tower filter circuit) are less than 5-micron in size. It is known that the water from the cooling tower absorbs most dirt and airborne contaminants surrounding the tower. Microorganisms and particles of that size produce fouling which can result in scale build-up and algae contamination. They also become food and support for bacteria.?
Recirculation flow, airborne contamination source, volume of water, make-up water quality... all these operation parameters are considered in sizing the proper cooling tower filter. Each Vortisand® cooling tower filter system offers the best solution that will truly fit your needs and provide clean, clear water, 100% of the time even when the cooling demand is at its peak.



cooling_tower_filter |
cooling tower water treatment | process water filtration | centrifugal separator | industrial water filters | cooling water filtration | RO pretreatment | cooling tower filtering | cooling water filter | industrial HVAC towers water filtration | sidestream filtration | water centrifugal separators | side stream filtration | hvac water filter | cooling tower filtration | centrifugal water separators | HVAC tower micron water filtration | cooling tower sand filter | cooling tower filter | industrial water filter | industrial water filtration systems |